Description
TeSys GV motor circuit breaker, 3 poles (3P), 14A/690V, for 3-phase motor applications 5.5kW@400V. It provides a thermal-magnetic protection with a thermal setting range 9-14A, magnetic tripping at 13xIn, high breaking capacity Icu 15kA@400V. Connection by screw clamp terminals. Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Details
Brand
SCHNEIDER ELECTRIC AUSTRALIA PTY LTD
Supplier Part No
GV2P16
Unit Of Measure
EA
Pack Size
1
Features
Adjustment range undelayed short-circuit release
170A to 0A
Brand
SCHNEIDER ELECTRIC
Connection type main current circuit
Screw connection
Degree of protection (IP)
IP20
Device construction
Complete device in housing
Number of poles
3
Phase failure sensitive
No
Rated operation power at AC-3, 400 V
5.5kW
Rated permanent current Iu
14A
Rated short-circuit breaking capacity lcu at 400 V, AC
100kA
Setting range overload protector
9A to 14A
Switch off technique
Thermomagnetic
UNSPSC
39121600
With integrated auxiliary switch
No
With integrated under voltage release